Modular I/O System BACnet/IP Controller 750-830 Manual Technical description, installation and configuration Version 1.0.1
10 • Important Notes Safety Information WAGO-I/O-SYSTEM 750 BACnet/IP Controller 1.4 Safety Information When connecting the device to your install
100 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.8.4.1 IEC Task Sequen
BACnet/IP Controller 750-830 • 101 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller Tab. 3-19: Task pri
102 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.8.5 System Events Fig
BACnet/IP Controller 750-830 • 103 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.8.6 Transfer o
104 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller The following standard ent
BACnet/IP Controller 750-830 • 105 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.8.6.2 Transfer
106 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.8.7 The Web-Based Man
BACnet/IP Controller 750-830 • 107 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller ETHERNET Over the &
108 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller A set data transfer rate c
BACnet/IP Controller 750-830 • 109 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller TCP/IP Click the li
Important Notes • 11 Font Conventions WAGO-I/O-SYSTEM 750 BACnet/IP Controller Warning For components with ETHERNET/RJ-45 connectors: Only f
110 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller Port Click the "Port&
BACnet/IP Controller 750-830 • 111 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller SNMP Click the link
112 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller Clock Click the link "
BACnet/IP Controller 750-830 • 113 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller Fig. 3-13: Web-ba
114 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller Security Click the "S
BACnet/IP Controller 750-830 • 115 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller Features Click the
116 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller MODBUS IP Click the link &
BACnet/IP Controller 750-830 • 117 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller MODBUS RTU Click th
118 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller BACnet You can set the tra
BACnet/IP Controller 750-830 • 119 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller PLC Click the "
12 • Important Notes Scope WAGO-I/O-SYSTEM 750 BACnet/IP Controller 1.7 Scope This manual describes the field bus independent WAGO I/O SYSTEM 750
120 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller Fig. 3-19: Web-based Man
BACnet/IP Controller 750-830 • 121 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller I/O config Click th
122 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller Fig. 3-21: Web-based Man
BACnet/IP Controller 750-830 • 123 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller WebVisu Use the lin
124 • BACnet/IP Controller 750-830 LED Signaling WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.9 LED Signaling For on-site diagnostics, the control
BACnet/IP Controller 750-830 • 125 LED Signaling WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.9.1 Fieldbus Status Communication status via
126 • BACnet/IP Controller 750-830 LED Signaling WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.9.2 Node Status – "I/O" LED Blink Code Ta
BACnet/IP Controller 750-830 • 127 LED Signaling WAGO-I/O-SYSTEM 750 BACnet/IP Controller After elimination of the error, the controller mu
128 • BACnet/IP Controller 750-830 LED Signaling WAGO-I/O-SYSTEM 750 BACnet/IP Controller "I/O" LED Error Messages as Blinking Sequences
BACnet/IP Controller 750-830 • 129 LED Signaling WAGO-I/O-SYSTEM 750 BACnet/IP Controller Error code 1: "Hardware and configuration er
System Description • 13 Technical Condition of the Devices WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2 The WAGO-I/O-SYSTEM 750 2.1 System De
130 • BACnet/IP Controller 750-830 LED Signaling WAGO-I/O-SYSTEM 750 BACnet/IP Controller Error code 3 “Protocol error internal bus” Error argumen
BACnet/IP Controller 750-830 • 131 LED Signaling WAGO-I/O-SYSTEM 750 BACnet/IP Controller Error code 4 "Physical error, internal bus&q
132 • BACnet/IP Controller 750-830 LED Signaling WAGO-I/O-SYSTEM 750 BACnet/IP Controller Error code 6 " Node configuration error " Erro
BACnet/IP Controller 750-830 • 133 LED Signaling WAGO-I/O-SYSTEM 750 BACnet/IP Controller Error code 10 "Error during PLC program proc
134 • BACnet/IP Controller 750-830 LED Signaling WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.9.4 Status supply voltage Tab. 3-26: Status supply
BACnet/IP Controller 750-830 • 135 Fault behavior WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.10 Fault behavior 3.1.10.1 Loss of Fieldbus
136 • BACnet/IP Controller 750-830 Fault behavior WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.10.2 Internal Bus Error An internal bus failure oc
BACnet/IP Controller 750-830 • 137 Technical Data WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.11 Technical Data System data System data ET
138 • BACnet/IP Controller 750-830 Technical Data WAGO-I/O-SYSTEM 750 BACnet/IP Controller Technical Data Voltage via power jumper contacts DC 24
BACnet/IP Controller 750-830 • 139 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12 BACnet Building
14 • Technical Data Technical Condition of the Devices WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.2 Technical Data Mechanic Material Polycarbona
140 • BACnet/IP Controller 750-830 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller • Ability to synchronize its int
BACnet/IP Controller 750-830 • 141 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12.1.1.1 Data Shari
142 • BACnet/IP Controller 750-830 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller Data Sharing-WriteProperty-B (DS-
BACnet/IP Controller 750-830 • 143 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller Data Sharing COVP-A (DS-
144 • BACnet/IP Controller 750-830 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12.1.1.2 Alarm and Event Man
BACnet/IP Controller 750-830 • 145 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12.1.1.3 Scheduling
146 • BACnet/IP Controller 750-830 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12.1.1.4 Trending BIBBs These
BACnet/IP Controller 750-830 • 147 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12.1.1.5 Device and
148 • BACnet/IP Controller 750-830 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller Device Management-DeviceCommunica
BACnet/IP Controller 750-830 • 149 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller Device Management-Backup
Technical Data • 15 Technical Condition of the Devices WAGO-I/O-SYSTEM 750 BACnet/IP Controller Safe electrical isolation Air and creepage
150 • BACnet/IP Controller 750-830 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12.2 "Native" Opera
BACnet/IP Controller 750-830 • 151 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12.2.1 Analog Input
152 • BACnet/IP Controller 750-830 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12.2.2 Analog Output Object
BACnet/IP Controller 750-830 • 153 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12.2.3 Binary Input
154 • BACnet/IP Controller 750-830 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller Property Data type: Default Val
BACnet/IP Controller 750-830 • 155 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12.2.4 Binary Outpu
156 • BACnet/IP Controller 750-830 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller Property Data type: Default Val
BACnet/IP Controller 750-830 • 157 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12.2.5 Calendar Obje
158 • BACnet/IP Controller 750-830 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12.2.6 Device Object The Devi
BACnet/IP Controller 750-830 • 159 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller Property Data type: De
16 • Technical Data Technical Condition of the Devices WAGO-I/O-SYSTEM 750 BACnet/IP Controller Mechanical strength acc. to IEC 61131-2 Test spec
160 • BACnet/IP Controller 750-830 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12.2.7 File Object A File Obj
BACnet/IP Controller 750-830 • 161 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.12.2.8 Schedule Obje
162 • BACnet/IP Controller 750-830 BACnet Building Controller (B-BC) WAGO-I/O-SYSTEM 750 BACnet/IP Controller Properties Data type: Based on
Fieldbus Communication • 163 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4 Fieldbus Communication 4.1 ETHERNET 4.1.1 General ETHERNET i
164 • Fieldbus Communication ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller The WAGO ETHERNET TCP/IP fieldbus node does not require any addi-ti
Fieldbus Communication • 165 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.1.2.1 Transmission Media General ETHERNET transmission stand
166 • Fieldbus Communication ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 10BaseT, 100BaseTX Either the 10BaseT standard or 100BaseTX can be
Fieldbus Communication • 167 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller Attention The cable length between the node and the hub can
168 • Fieldbus Communication ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller Tree Topology The tree topology combines characteristics of linear
Fieldbus Communication • 169 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 5-4-3 Rule A consideration in setting up a tree topology using
Technical Data • 17 Technical Condition of the Devices WAGO-I/O-SYSTEM 750 BACnet/IP Controller For Products of the WAGO-I/O-SYSTEM 750 wit
170 • Fieldbus Communication ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.1.2.3 Coupler Modules There are a number of hardware modules that
Fieldbus Communication • 171 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.1.2.4.1 Static Configuration of the Transmission Mode Using
172 • Fieldbus Communication ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.1.2.5 Important Terms Data security If an internal network (Intr
Fieldbus Communication • 173 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller Deterministic ETHERNET The TCP/IP software or the user progr
174 • Fieldbus Communication ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.1.3 Network Communication Fieldbus communication between master a
Fieldbus Communication • 175 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller data and the resultant increase in processing speed. Many
176 • Fieldbus Communication ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.1.3.2 Communication Protocols In addition to the ETHERNET standar
Fieldbus Communication • 177 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.1.3.2.1 ETHERNET ETHERNET address (MAC-ID) Each WAGO ETHERNE
178 • Fieldbus Communication ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.1.3.2.1.1 Channel access method In the ETHERNET Standard, the fi
Fieldbus Communication • 179 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller Class A: (Net-ID: Byte1, Host-ID: Byte2 - Byte4) e.g.: 101
18 • Technical Data Technical Condition of the Devices WAGO-I/O-SYSTEM 750 BACnet/IP Controller Range of application Required specification emi
180 • Fieldbus Communication ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller Attention Never set all bits to equal 0 or 1 in one byte (byte =
Fieldbus Communication • 181 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller The standard masks depending upon the respective network class
182 • Fieldbus Communication ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller Gateway The subnets of the Internet are normally connected via gate
Fieldbus Communication • 183 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.1.3.2.2.1 RAW IP Raw IP manages without protocols such as PP
184 • Fieldbus Communication ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller TCP port numbers TCP can, in addition to the IP address (network an
Fieldbus Communication • 185 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.1.3.3 Administration and Diagnosis Protocols In addition to
186 • Fieldbus Communication ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller The BOOTP Client allows for dynamic configuring of the network para
Fieldbus Communication • 187 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.1.3.3.2 HTTP (Hyper Text Transfer Protocol) HTTP is a proto
188 • Fieldbus Communication ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller In the case of configuration of network parameters via the DHCP pro
Fieldbus Communication • 189 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.1.3.3.6 FTP-Server (File Transfer Protocol) The file transf
Technical Data • 19 Technical Condition of the Devices WAGO-I/O-SYSTEM 750 BACnet/IP Controller Dimensions 5124V 0V++--0102CDBACDBACDBACDB
190 • Fieldbus Communication ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller Command Function NLST Gives the directory list RMD Deletes direct
Fieldbus Communication • 191 ETHERNET WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.1.3.4 Application Protocols If fieldbus specific application
192 • Fieldbus Communication BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.2 BACnet/IP 4.2.1 General The "Building Automation and Cont
Fieldbus Communication • 193 BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.2.1.2.1 Objects BACnet offers a unified structure for diffe
194 • Fieldbus Communication BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller Object Function 20 Multi-State Value Multi-level value, deliver
Fieldbus Communication • 195 BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.2.1.2.3 Services BACnet is based on the Client-Server model
196 • Fieldbus Communication BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller • ConfirmedEventNotification Service Informs of an event that has
Fieldbus Communication • 197 BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller • WritePropertyMultiple Service Changes the values of severa
198 • Fieldbus Communication BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller Virtual terminal services (Virtual Terminal Service) • VT-Open S
Fieldbus Communication • 199 BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller Tab. 4-37: Priority levels Priority Level Use 1 (high) Man
2 • General WAGO-I/O-SYSTEM 750 BACnet/IP Controller Copyright © 2008 by WAGO Kontakttechnik GmbH & Co. KG All rights reserved. The co
20 • Manufacturing Number Technical Condition of the Devices WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.3 Manufacturing Number The manufacturing
200 • Fieldbus Communication BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller __________________________________________________________________
Fieldbus Communication • 201 BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller _____________________________________________________________
202 • Fieldbus Communication BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.2.1.2.4 Interoperability Area (IA) The requirements for the ove
Fieldbus Communication • 203 BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller Example: AE-N-A Alarm and Event-Notification-A The Client (A
204 • Fieldbus Communication BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.2.1.2.4.5 Device Management (DM) Information on state, presence
Fieldbus Communication • 205 BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.2.1.2.6 Protocol Implementation Conformance Statement (PICS
206 • Fieldbus Communication BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller Tab. 4-38: IAs/BIBBs of the six standardized device profiles B-OW
Fieldbus Communication • 207 BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.2.1.2.8 BACnet Components in Overview The following illustr
208 • Fieldbus Communication BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.2.1.3 Scope of Use in Building Automation The use of BACnet dev
Fieldbus Communication • 209 BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.2.1.4.1 Automation Level The automation level includes alar
Component Update • 21 Technical Condition of the Devices WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.4 Component Update For the case of an Up
210 • Fieldbus Communication BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller BACnet Application Layer This layer represents the application
Fieldbus Communication • 211 BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.2.1.6 BACnet in the Network There are 2 possibilities for
212 • Fieldbus Communication BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.2.1.6.2 BACnet/IP For data transmission via BACnet/IP, each indi
Fieldbus Communication • 213 BACnet/IP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.2.1.6.2.2 BACnet/IP in Foreign Networks If a device is con
214 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3 MODBUS Functions 4.3.1 General MODBUS is a manufacturer
Fieldbus Communication • 215 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller Therefore the MODBUS protocol based essentially on the
216 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.2 Use of the MODBUS Functions The example below uses a
Fieldbus Communication • 217 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.3 Description of the MODBUS Functions All MODBUS
218 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.3.1 Function Code FC1 (Read Coils) This function reads
Fieldbus Communication • 219 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.3.2 Function Code FC2 (Read Input Discretes) This
22 • Mechanical Setup Installation Position WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.6 Mechanical Setup 2.6.1 Installation Position Along with h
220 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.3.3 Function Code FC3 (Read multiple registers) This f
Fieldbus Communication • 221 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.3.4 Function code FC4 (Read input registers) This
222 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.3.5 Function Code FC5 (Write Coil) This function write
Fieldbus Communication • 223 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.3.6 Function Code FC6 (Write single register) Thi
224 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.3.7 Function Code FC11 (Get comm event counter) This f
Fieldbus Communication • 225 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.3.8 Function Code FC15 (Force Multiple Coils) Th
226 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.3.9 Function Code FC16 (Write multiple registers) Thi
Fieldbus Communication • 227 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.3.10 Function Code FC22 (Mask Write Register) Th
228 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.3.11 Function Code FC23 (Read/Write multiple registers
Fieldbus Communication • 229 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.4 MODBUS Register Mapping The following tables di
Mechanical Setup • 23 Assembly onto Carrier Rail WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.6.3 Assembly onto Carrier Rail 2.6.3.1 Carrier
230 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller MODBUS-Address IEC61131[dec] [hex] AddressMemory Range 12
Fieldbus Communication • 231 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller Bit Access Writing (with FC5 and FC15): MODBUS Address
232 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller Address Access Length (word) Remark 0x1029 R 9 MODBUS-TC
Fieldbus Communication • 233 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.5.1 Description of the internal variables 4.3.5.1
234 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller Register address 0x1001 (MODBUS Address 404098) Designation
Fieldbus Communication • 235 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller Register address 0x1005 (MODBUS Address 404102) Design
236 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller Register address 0x100A (MODBUS Address 404107) Designation
Fieldbus Communication • 237 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller Register address 0x100B Value Save Watchdog Parameter
238 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller Register address 0x1024 (MODBUS Address 404133) Designation
Fieldbus Communication • 239 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller Register address 0x102A (MODBUS Address 404139, with a
24 • Mechanical Setup Spacing WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.6.3.2 WAGO DIN Rail WAGO carrier rails meet the electrical and mechanica
240 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller Examples: 4 Channel Digital Input Module = 0x8401 bit 15 14
Fieldbus Communication • 241 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller Register address 0x2033 (MODBUS Address 408244, with a
242 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4.3.5.4 Firmware Information The following registers contai
Fieldbus Communication • 243 MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller Register address 0x2021 (MODBUS Address 408226, with a
244 • Fieldbus Communication MODBUS Functions WAGO-I/O-SYSTEM 750 BACnet/IP Controller Register address 0x2003 (MODBUS Address 408196) Value Mask
I/O Modules • 245 Overview WAGO-I/O-SYSTEM 750 BACnet/IP Controller 5 I/O Modules 5.1 Overview All listed bus modules, in the overview
246 • I/O Modules Overview WAGO-I/O-SYSTEM 750 BACnet/IP Controller 750-432, 753-432 4 Channel, DC 24 V, 3.0 ms, 2-conductor connection; high-
I/O Modules • 247 Overview WAGO-I/O-SYSTEM 750 BACnet/IP Controller DI NAMUR 750-435 1 Channel, NAMUR EEx i, proximity switch acc. to DI
248 • I/O Modules Overview WAGO-I/O-SYSTEM 750 BACnet/IP Controller DO AC/DC 230 V 750-509, 753-509 2 Channel solid state relay, AC/DC 230 V, 3
I/O Modules • 249 Overview WAGO-I/O-SYSTEM 750 BACnet/IP Controller AI 0 - 10 V 750-467, 753-467 2 Channel, DC 0 - 10 V, single-ended 75
Mechanical Setup • 25 Plugging and Removal of the Components WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.6.5 Plugging and Removal of the Com
250 • I/O Modules Overview WAGO-I/O-SYSTEM 750 BACnet/IP Controller 5.1.4 Analog Output Modules Tab. 5-4: Analog output modules AO 0 - 20 mA 75
I/O Modules • 251 Overview WAGO-I/O-SYSTEM 750 BACnet/IP Controller 5.1.5 Special Modules Tab. 5-5: Special modules Counter Modules 750-4
252 • I/O Modules Overview WAGO-I/O-SYSTEM 750 BACnet/IP Controller PROFIsafe Modules 750-660/000-001 8FDI 24V DC PROFIsafe; PROFIsafe 8 channe
I/O Modules • 253 Overview WAGO-I/O-SYSTEM 750 BACnet/IP Controller 5.1.6 System Modules Tab. 5-6: System modules Module Bus Extension 75
254 • I/O Modules Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 5.2 Process Data Architecture for MODBUS/T
I/O Modules • 255 Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2 Channel Digital Input Modules 750
256 • I/O Modules Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4 Channel Digital Input Modules 750-402, -4
I/O Modules • 257 Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2 Channel Digital Output Modules 75
258 • I/O Modules Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller Input Process Image Bit 7 Bit 6 Bit 5 Bi
I/O Modules • 259 Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller Output Process Image Bit 7 Bit 6
26 • Mechanical Setup Assembly Sequence WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.6.6 Assembly Sequence All system components can be snapped dire
260 • I/O Modules Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 5.2.3 Analog Input Modules The hardware of
I/O Modules • 261 Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4 Channel Analog Input Modules 750-
262 • I/O Modules Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4 Channel Analog Output Modules 750-553, -5
I/O Modules • 263 Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller Input Process Image Byte Destinatio
264 • I/O Modules Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 750-638, 753-638 The above Counter Modules
I/O Modules • 265 Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller Pulse Width Modules 750-511, (and a
266 • I/O Modules Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller Serial Interface Modules with Standard Data
I/O Modules • 267 Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller SSI Transmitter Interface Modules 7
268 • I/O Modules Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 750-634 The above Incremental Encoder Inter
I/O Modules • 269 Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 750-635, 753-635 The above Digital
Mechanical Setup • 27 Internal Bus/Data Contacts WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.6.7 Internal Bus/Data Contacts Communication be
270 • I/O Modules Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller Input Process Image Byte Destination Offse
I/O Modules • 271 Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller MP Bus Master Module 750-643 The MP
272 • I/O Modules Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller Vibration Velocity/Bearing Condition Monito
I/O Modules • 273 Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller AS-interface Master Module 750-655
274 • I/O Modules Process Data Architecture for MODBUS/TCP WAGO-I/O-SYSTEM 750 BACnet/IP Controller 5.2.6 System Modules System Modules with Di
List of all BACnet Properties in Native Operation • 275 WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6 List of all BACnet Properties in Na
276 • List of all BACnet Properties in Native Operation Acked_Transitions WAGO-I/O-SYSTEM 750 BACnet/IP Controller The difference between the pr
List of all BACnet Properties in Native Operation • 277 Active_COV_Subscriptions WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.2 Active_COV
278 • List of all BACnet Properties in Native Operation Alarm_Value WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.4 Alarm_Value Data Type BACnetBin
List of all BACnet Properties in Native Operation • 279 APDU_Segment_Timeout WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.5 APDU_Segment_T
28 • Mechanical Setup Power Contacts WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.6.8 Power Contacts Self-cleaning power contacts , are situated on
280 • List of all BACnet Properties in Native Operation Application_Software_Version WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.7 Application_So
List of all BACnet Properties in Native Operation • 281 Change_Of_State_Count WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.10 Change_Of_St
282 • List of all BACnet Properties in Native Operation Configuration_Files WAGO-I/O-SYSTEM 750 BACnet/IP Controller Change_Of_State_Count, or T
List of all BACnet Properties in Native Operation • 283 Data_List WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.15 Data_List Data Type Lis
284 • List of all BACnet Properties in Native Operation Description WAGO-I/O-SYSTEM 750 BACnet/IP Controller • the Present_Value must fall belo
List of all BACnet Properties in Native Operation • 285 Device_Type WAGO-I/O-SYSTEM 750 BACnet/IP Controller may be empty if no device i
286 • List of all BACnet Properties in Native Operation Event_Enable WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.23 Event_Enable Data Type BACnet
List of all BACnet Properties in Native Operation • 287 Exception_Schedule WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.26 Exception_Sched
288 • List of all BACnet Properties in Native Operation Feedback_Value WAGO-I/O-SYSTEM 750 BACnet/IP Controller plies to a given day, the relati
List of all BACnet Properties in Native Operation • 289 File_Size WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.29 File_Size Data Type Uns
Mechanical Setup • 29 Wire Connection WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.6.9 Wire Connection All components have CAGE CLAMP® connecti
290 • List of all BACnet Properties in Native Operation Inactive_Text WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.33 Inactive_Text Data Type Char
List of all BACnet Properties in Native Operation • 291 Limit_Enable WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.35 Limit_Enable Data Typ
292 • List of all BACnet Properties in Native Operation Local_Date WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.37 Local_Date Data Type Date Obje
List of all BACnet Properties in Native Operation • 293 Max_APDU_Length_Accepted WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.41 Max_APDU_
294 • List of all BACnet Properties in Native Operation Minimum_Off_Time WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.45 Minimum_Off_Time Data Typ
List of all BACnet Properties in Native Operation • 295 Modification_Date WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.48 Modification_Dat
296 • List of all BACnet Properties in Native Operation Object_Identifier WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.52 Object_Identifier Data T
List of all BACnet Properties in Native Operation • 297 Object_Type WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.55 Object_Type Data Type
298 • List of all BACnet Properties in Native Operation Polarity WAGO-I/O-SYSTEM 750 BACnet/IP Controller Schedule: The Out_Of_Service property
List of all BACnet Properties in Native Operation • 299 Present_Value WAGO-I/O-SYSTEM 750 BACnet/IP Controller Tab. 6-7: Interrelations
Content • 3 WAGO-I/O-SYSTEM 750 BACnet/IP Controller Content 1 Important Notes ...
30 • Power Supply Isolation WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.7 Power Supply 2.7.1 Isolation Within the field bus node, there are three e
300 • List of all BACnet Properties in Native Operation Present_Value WAGO-I/O-SYSTEM 750 BACnet/IP Controller Binary Output: For this object, t
List of all BACnet Properties in Native Operation • 301 Present_Value WAGO-I/O-SYSTEM 750 BACnet/IP Controller The normal calculation of
302 • List of all BACnet Properties in Native Operation Priority_Array WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.59 Priority_Array Data Type B
List of all BACnet Properties in Native Operation • 303 Protocol_Revision WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.62 Protocol_Revisio
304 • List of all BACnet Properties in Native Operation Read_Only WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.65 Read_Only Data Type BOOLEAN Obje
List of all BACnet Properties in Native Operation • 305 Relinquish_Default WAGO-I/O-SYSTEM 750 BACnet/IP Controller Binary Input: {NO_F
306 • List of all BACnet Properties in Native Operation Resolution WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.69 Resolution Data Type REAL Obje
List of all BACnet Properties in Native Operation • 307 Status_Flags WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.72 Status_Flags Data Typ
308 • List of all BACnet Properties in Native Operation System_Status WAGO-I/O-SYSTEM 750 BACnet/IP Controller • Schedule: Logical TRUE (1) if
List of all BACnet Properties in Native Operation • 309 Time_Of_Active_Time_Reset WAGO-I/O-SYSTEM 750 BACnet/IP Controller Analog Input,
Power Supply • 31 System Supply WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.7.2 System Supply 2.7.2.1 Connection The WAGO-I/O-SYSTEM 750 requ
310 • List of all BACnet Properties in Native Operation Update_Interval WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.78 Update_Interval Data Type
List of all BACnet Properties in Native Operation • 311 Vendor_Name WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.81 Vendor_Name Data Type
312 • Protocol Implementation Conformance Statement (PICS) PICS Content WAGO-I/O-SYSTEM 750 BACnet/IP Controller 7 Protocol Implementation Conf
Application Examples • 313 Test of MODBUS Protocol and Fieldbus Nodes WAGO-I/O-SYSTEM 750 BACnet/IP Controller 8 Application Examples 8.1 T
314 • Application Examples Visualization and Control Using SCADA Software WAGO-I/O-SYSTEM 750 BACnet/IP Controller SCADA Systems functions includ
Application Examples • 315 Visualization and Control Using SCADA Software WAGO-I/O-SYSTEM 750 BACnet/IP Controller Example for MODBUS functi
316 • Use in Hazardous Environments Foreword WAGO-I/O-SYSTEM 750 BACnet/IP Controller 9 Use in Hazardous Environments 9.1 Foreword Today’s develo
Use in Hazardous Environments • 317 Classification Meeting CENELEC and IEC WAGO-I/O-SYSTEM 750 BACnet/IP Controller Explosive areas resulti
318 • Use in Hazardous Environments Classification Meeting CENELEC and IEC WAGO-I/O-SYSTEM 750 BACnet/IP Controller 9.3.2 Device Group In addition
Use in Hazardous Environments • 319 Classification Meeting CENELEC and IEC WAGO-I/O-SYSTEM 750 BACnet/IP Controller 9.3.3 Unit Categories A
32 • Power Supply System Supply WAGO-I/O-SYSTEM 750 BACnet/IP Controller Attention Resetting the system by switching on and off the system supp
320 • Use in Hazardous Environments Classification Meeting CENELEC and IEC WAGO-I/O-SYSTEM 750 BACnet/IP Controller 9.3.4 Temperature Classes The
Use in Hazardous Environments • 321 Classification Meeting CENELEC and IEC WAGO-I/O-SYSTEM 750 BACnet/IP Controller 9.3.5 Types of Ignitio
322 • Use in Hazardous Environments Classification Meeting CENELEC and IEC WAGO-I/O-SYSTEM 750 BACnet/IP Controller • Apparatus with protected co
Use in Hazardous Environments • 323 Classifications Meeting the NEC 500 WAGO-I/O-SYSTEM 750 BACnet/IP Controller 9.4 Classifications Meet
324 • Use in Hazardous Environments Classifications Meeting the NEC 500 WAGO-I/O-SYSTEM 750 BACnet/IP Controller 9.4.3 Temperature Classes Electr
Use in Hazardous Environments • 325 Identification WAGO-I/O-SYSTEM 750 BACnet/IP Controller 9.5 Identification 9.5.1 For Europe According t
326 • Use in Hazardous Environments Identification WAGO-I/O-SYSTEM 750 BACnet/IP Controller 9.5.2 For America According to NEC 500 Fig. 9.5.2-3:
Use in Hazardous Environments • 327 Installation Regulations WAGO-I/O-SYSTEM 750 BACnet/IP Controller 9.6 Installation Regulations In the F
328 • Use in Hazardous Environments Installation Regulations WAGO-I/O-SYSTEM 750 BACnet/IP Controller 9.6.1 ANSI/ISA 12.12.01 This equipment is su
Use in Hazardous Environments • 329 Installation Regulations WAGO-I/O-SYSTEM 750 BACnet/IP Controller 9.6.2 TÜV Nord Ex-i applications Fo
Power Supply • 33 System Supply WAGO-I/O-SYSTEM 750 BACnet/IP Controller Example: A node with a PROFIBUS Coupler 750-333 consists of 20 rela
330 • Use in Hazardous Environments Installation Regulations WAGO-I/O-SYSTEM 750 BACnet/IP Controller 9.6.3 ATEX and IEC Ex GROUP I, CATEGORY M2
Glossary • 331 WAGO-I/O-SYSTEM 750 BACnet/IP Controller Glossary A ASHRAE (American Society of Heating, Refrigerating and Air-Conditio
332 • Glossary WAGO-I/O-SYSTEM 750 BACnet/IP Controller BACnet Configurator The BACnet Configurator is free software that is used for com
Glossary • 333 WAGO-I/O-SYSTEM 750 BACnet/IP Controller BACstac Function libraries that implement the BACnet protocol and interfaces wit
334 • Glossary WAGO-I/O-SYSTEM 750 BACnet/IP Controller BIBB (BACnet Interoperability Building Block) A BIBB defines which BACnet feature
Glossary • 335 WAGO-I/O-SYSTEM 750 BACnet/IP Controller Bridge A bridge runs on Layer 2 of the ISO/OSI model. Although the bridge corre-
336 • Glossary WAGO-I/O-SYSTEM 750 BACnet/IP Controller Coaxial Cable This cable contains one, single conductor and radial shielding for
Glossary • 337 WAGO-I/O-SYSTEM 750 BACnet/IP Controller DHCP (Dynamic Host Configuration Protocol) This protocol permits automatic confi
338 • Glossary WAGO-I/O-SYSTEM 750 BACnet/IP Controller E EDE (Electronic Data Exchange) The EDE file serves as a configuration aid for
Glossary • 339 WAGO-I/O-SYSTEM 750 BACnet/IP Controller F Fieldbus The fieldbus is a dedicated bus for the serial transmission of infor
34 • Power Supply Field Supply WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.7.3 Field Supply 2.7.3.1 Connection Sensors and actuators can be directl
340 • Glossary WAGO-I/O-SYSTEM 750 BACnet/IP Controller G Gateway Device for connecting two different networks, performs the translation
Glossary • 341 WAGO-I/O-SYSTEM 750 BACnet/IP Controller Hypertext Document format used by HTTP. Hypertext documents are text files that
342 • Glossary WAGO-I/O-SYSTEM 750 BACnet/IP Controller Internet A collection of networks interconnected to each other throughout the wor
Glossary • 343 WAGO-I/O-SYSTEM 750 BACnet/IP Controller IP Message Tunneling In addition to BACnet/IP, IP message tunneling is a method
344 • Glossary WAGO-I/O-SYSTEM 750 BACnet/IP Controller L LAN (Local Area Network) A LAN is a spatially limited, local network for perma
Glossary • 345 WAGO-I/O-SYSTEM 750 BACnet/IP Controller N Natives BACnet "Native" BACnet objects are those objects that are r
346 • Glossary WAGO-I/O-SYSTEM 750 BACnet/IP Controller Operating System An operating system is a software used for managing equipment su
Glossary • 347 WAGO-I/O-SYSTEM 750 BACnet/IP Controller Property Objects are described by specific properties and values. In this manner
348 • Glossary WAGO-I/O-SYSTEM 750 BACnet/IP Controller R Repeater Repeaters operate (like hubs, but with only one, instead of several o
Glossary • 349 WAGO-I/O-SYSTEM 750 BACnet/IP Controller RS232 The RS232 (official designation ANSI/EIA/TIA-232-F-1997) is a serial in-te
Power Supply • 35 Field Supply WAGO-I/O-SYSTEM 750 BACnet/IP Controller Attention Some bus modules have no or very few power contacts (de
350 • Glossary WAGO-I/O-SYSTEM 750 BACnet/IP Controller Service port The service port is located next to the mode switch, behind the cove
Glossary • 351 WAGO-I/O-SYSTEM 750 BACnet/IP Controller Structured Cabling With structured cabling, maximum permissible cable lengths ar
352 • Glossary WAGO-I/O-SYSTEM 750 BACnet/IP Controller T TCP (Transport Control Protocol) TCP is a connection-oriented network protocol
Glossary • 353 WAGO-I/O-SYSTEM 750 BACnet/IP Controller U UDP (Users Datagram Protocol) The user datagram protocol is a communication p
354 • Glossary WAGO-I/O-SYSTEM 750 BACnet/IP Controller W WAGO-I/O-PRO CAA (CoDeSys Automation Alliance) Uniform programming environment
Literature List • 355 WAGO-I/O-SYSTEM 750 BACnet/IP Controller Literature List Switching Technology in the Local Network Mathias Hein T
356 • Index WAGO-I/O-SYSTEM 750 BACnet/IP Controller Index 1 100BaseFX · 164 100BaseT4 · 164 100BaseTX · 46, 50 10BaseT · 46, 165 A Absol
Index • 357 WAGO-I/O-SYSTEM 750 BACnet/IP Controller F Fault behavior · 134 Field Level · 208 Fieldbus · 337 Connection · 50 Failure · 2
358 • Index WAGO-I/O-SYSTEM 750 BACnet/IP Controller PFC application · 54 PFC Cycle · 55 Ping command · 345 Port number · 183, 213, 345 P
Index • 359 WAGO-I/O-SYSTEM 750 BACnet/IP Controller
36 • Power Supply Field Supply WAGO-I/O-SYSTEM 750 BACnet/IP Controller Warning In the case of power supply modules with fuse holders, only fus
WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 • D-32385 Minden Hansastraße 27 • D-32423 Minden Phone: 05 71/8 87 – 0 Fax: 05 71/8 87 –
Power Supply • 37 Field Supply WAGO-I/O-SYSTEM 750 BACnet/IP Controller Alternatively, fusing can be done externally. The fuse modules of th
38 • Power Supply Supplementary Power Supply Regulations WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.7.4 Supplementary Power Supply Regulations T
Power Supply • 39 Supply Example WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.7.5 Supply Example Attention The system supply and the field
4 • Content WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.12 Configuration_Files...
40 • Power Supply Power Supply Unit WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.7.6 Power Supply Unit The WAGO-I/O-SYSTEM 750 requires a 24 V dir
Grounding • 41 Grounding the DIN Rail WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.8 Grounding 2.8.1 Grounding the DIN Rail 2.8.1.1 Framewor
42 • Grounding Grounding Function WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.8.2 Grounding Function The grounding function increases the resistanc
Grounding • 43 Grounding Protection WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.8.3 Grounding Protection For the field side, the ground wire
44 • Shielding (Screening) General WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.9 Shielding (Screening) 2.9.1 General The shielding of the data and
Assembly Guidelines/Standards • 45 WAGO Shield (Screen) Connecting System WAGO-I/O-SYSTEM 750 BACnet/IP Controller 2.9.4 WAGO Shield (Scree
46 • BACnet/IP Controller 750-830 Description WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3 Fieldbus Controller 3.1 BACnet/IP Controller 750-830 3.1
BACnet/IP Controller 750-830 • 47 Compatibility WAGO-I/O-SYSTEM 750 BACnet/IP Controller An application program can be created using the WA
48 • BACnet/IP Controller 750-830 Hardware WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.3 Hardware 3.1.3.1 View 24V 0V++_0102750-830LINKACTBTMSI/O
BACnet/IP Controller 750-830 • 49 Hardware WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.3.2 Power Supply The power supply is derived from m
Content • 5 WAGO-I/O-SYSTEM 750 BACnet/IP Controller 6.60 Priority_For_Writing...
50 • BACnet/IP Controller 750-830 Hardware WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.3.3 Fieldbus Connection The connection to the fieldbus is
BACnet/IP Controller 750-830 • 51 Hardware WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.3.4 Indicators The operational status for the field
52 • BACnet/IP Controller 750-830 Hardware WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.3.5 Configuration Interface and Programming Interface The
BACnet/IP Controller 750-830 • 53 Hardware WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.3.6 Mode Selector Switch The mode selector switch
54 • BACnet/IP Controller 750-830 Hardware WAGO-I/O-SYSTEM 750 BACnet/IP Controller Note The position of the mode selector switch is not import
BACnet/IP Controller 750-830 • 55 Operating System WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.4 Operating System 3.1.4.1 Boot-up Notic
56 • BACnet/IP Controller 750-830 Operating System WAGO-I/O-SYSTEM 750 BACnet/IP Controller Variables are set to 0 or FALSEor to their initial val
BACnet/IP Controller 750-830 • 57 Process Image WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.5 Process Image Sections 3.1.5 and 3.1.6 provi
58 • BACnet/IP Controller 750-830 Process Image WAGO-I/O-SYSTEM 750 BACnet/IP Controller Note If a node is changed or expanded, this may result
BACnet/IP Controller 750-830 • 59 Process Image WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.5.2 Example of an Input Process Image The fol
6 • Important Notes Legal Principles WAGO-I/O-SYSTEM 750 BACnet/IP Controller 1 Important Notes This section provides only a summary of the most i
60 • BACnet/IP Controller 750-830 Process Image WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.5.3 Example of an Output Data Process Image The foll
BACnet/IP Controller 750-830 • 61 Process Image WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.5.4 MODBUS Process Data For some bus modules
62 • BACnet/IP Controller 750-830 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.6 Data Exchange Exchange of process data takes place
BACnet/IP Controller 750-830 • 63 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.6.1 Memory Areas Programmable Fieldbus Control
64 • BACnet/IP Controller 750-830 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller In addition, all output data is mirrored in the BACnet/IP
BACnet/IP Controller 750-830 • 65 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.6.2 Addressing Module inputs and outputs in a
66 • BACnet/IP Controller 750-830 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.6.2.1 Addressing of Bus Modules Addressing first refe
BACnet/IP Controller 750-830 • 67 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.6.2.2 Example of Addressing Two digital input
68 • BACnet/IP Controller 750-830 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.6.2.3 Address Ranges Subdivision of the address range
BACnet/IP Controller 750-830 • 69 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller Word 512-1275: Second address range for the input/
Important Notes • 7 Legal Principles WAGO-I/O-SYSTEM 750 BACnet/IP Controller All personnel must be familiar with the applicable standards. W
70 • BACnet/IP Controller 750-830 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.6.2.4 Absolute Addressing Direct presentation of in
BACnet/IP Controller 750-830 • 71 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller Calculating addresses (as a function of the word a
72 • BACnet/IP Controller 750-830 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller 0x00000x00FF0x0000(0x0200)00x0FF(0x02FF)0x60000x62FC0x60
BACnet/IP Controller 750-830 • 73 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.6.4 Data Exchange between PLC Function (CPU)
74 • BACnet/IP Controller 750-830 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.6.5.1 Example of MODBUS/TCP Master and PLC Function
BACnet/IP Controller 750-830 • 75 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.6.5.2 Juxtaposition of MODBUS/TCP and IEC 611
76 • BACnet/IP Controller 750-830 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.6.5.2.2 Bit Access Tab. 3-16: Bit access MODBUS Addre
BACnet/IP Controller 750-830 • 77 Data Exchange WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.6.5.2.3 Application Example Bit 1Bit 4Word2Wor
78 • BACnet/IP Controller 750-830 Fieldbus Node Start-up WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.7 Fieldbus Node Start-up This chapter prov
BACnet/IP Controller 750-830 • 79 Fieldbus Node Start-up WAGO-I/O-SYSTEM 750 BACnet/IP Controller After a brief period, the 'I/O&apos
8 • Important Notes Standards and Regulations for Operating the 750 Series WAGO-I/O-SYSTEM 750 BACnet/IP Controller 1.2 Standards and Regulation
80 • BACnet/IP Controller 750-830 Fieldbus Node Start-up WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.7.1.3 Testing for Proper Functioning of th
BACnet/IP Controller 750-830 • 81 Fieldbus Node Start-up WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.7.2 Commissioning with the WAGO Boo
82 • BACnet/IP Controller 750-830 Fieldbus Node Start-up WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.7.2.2 Connecting Client PC and Fieldbus Nod
BACnet/IP Controller 750-830 • 83 Fieldbus Node Start-up WAGO-I/O-SYSTEM 750 BACnet/IP Controller 4. In the dialog window that then appea
84 • BACnet/IP Controller 750-830 Fieldbus Node Start-up WAGO-I/O-SYSTEM 750 BACnet/IP Controller Note It is also possible to assign IP addres
BACnet/IP Controller 750-830 • 85 Fieldbus Node Start-up WAGO-I/O-SYSTEM 750 BACnet/IP Controller The examples shown contain the following
86 • BACnet/IP Controller 750-830 Fieldbus Node Start-up WAGO-I/O-SYSTEM 750 BACnet/IP Controller Note To address additional fieldbus nodes, ent
BACnet/IP Controller 750-830 • 87 Fieldbus Node Start-up WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.7.2.5 Testing the Function of the F
88 • BACnet/IP Controller 750-830 Fieldbus Node Start-up WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.7.2.6 Deactivating the BootP Protocol By de
BACnet/IP Controller 750-830 • 89 Fieldbus Node Start-up WAGO-I/O-SYSTEM 750 BACnet/IP Controller Fig. 3-2: HTML pages of the Web-based
Important Notes • 9 Symbols WAGO-I/O-SYSTEM 750 BACnet/IP Controller 1.3 Symbols Danger Always observe this information to protect persons f
90 • BACnet/IP Controller 750-830 Fieldbus Node Start-up WAGO-I/O-SYSTEM 750 BACnet/IP Controller Fig. 3-3: Port configuration G083052e You ar
BACnet/IP Controller 750-830 • 91 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.8 Programming t
92 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller To ensure that you can acce
BACnet/IP Controller 750-830 • 93 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller Note The number o
94 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller Fig. 3-5: Write access ove
BACnet/IP Controller 750-830 • 95 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller The file already con
96 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.8.2 Creating/Exporting
BACnet/IP Controller 750-830 • 97 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.8.3 ETHERNET Li
98 • BACnet/IP Controller 750-830 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller Additional Information F
BACnet/IP Controller 750-830 • 99 Programming the PFC Using WAGO-I/O-PRO CAA WAGO-I/O-SYSTEM 750 BACnet/IP Controller 3.1.8.4 General Inf