284 • List of all BACnet Properties in Native Operation
Description
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
the Present_Value must fall below the High_Limit
minus Deadband, and
the Present_Value must exceed the Low_Limit plus
the Deadband, and
the Present_Value must remain within this range for
a minimum period of time, specified in the
Time_Delay property, and
either the HighLimitEnable or LowLimitEnable flag
must be set in the Limit_Enable property, and
the TO-NORMAL flag must be enabled in the
Event_Enable property.
This property is required if intrinsic reporting is supported
by this object.
6.18 Description
Data Type CharacterString
Objects File, Binary input, Binary output, Analog input, Analog out-
put, Device, Calendar, Scheduler
Description This property, of type CharacterString, is a string of print-
able characters that may be used to describe the application
being carried out by the BACnet Device or other locally de-
sired descriptive information.
6.19 Device_Address_Binding
Data Type List of BACnetAddressBinding
Objects Device
Description The Device_Address_Binding property is a List of
BACnetAddressBinding each of which consists of a
BACnet Object_Identifier of a BACnet Device object and a
BACnet device address in the form of a BACnetAddress.
Entries in the list identify the actual device addresses that
will be used when the remote device must be accessed via a
BACnet service request. A value of zero is used for the net-
work number portion of BACnetAddress entries for other
devices residing on the same network as this device. The list